top of page

 Protective enclosures 

We offer protective enclosures as clean room solutions

Clean room quality up to DIN EN ISO 14644 / ISO 5

 

Industries that productively use our protective enclosures:

Pharmaceutical / microelectronics / automotive / food industry / medical technology

DIN and ISO standard

We build our protective enclosures independently in cleanroom quality  DIN EN ISO 14644 / ISO 5 

Elements

 Makrolon  ( colorless / transparent ) also ESD-capable

Polycarbonates (abbreviated PC) are thermoplastics. They are formally polyesters of carbonic acid.

 Laminated safety glass 

 

Laminated safety glass is a laminate consisting of two or more flat glass panes connected by a tear-resistant and viscoplastic film. It has several safety features (impact resistant, significantly lower risk of injury from splinters) compared to a simple glass, as well as significantly higher sound insulation. It was available as Sigla multilayer glass by the mid-1930s.

 Aluminum composite panels in pure white 

Aluminum composite panels are materials that consist of several different layers. They are also so-called sandwich panels. The two outer layers consist of 0.1-0.3mm thick aluminum sheets thermally bonded to an inner polyethylene core. Structure: ALU-plastic-ALU. The thickness of the plastic core can vary, so that panels with a total thickness of 2-6mm can be produced.

 Hard foam panels in pure white 

Rigid PVC foam panels are used wherever the properties of the material PVC but weight needs to be saved. By using rigid PVC foam, you save more than 50% in weight compared to rigid PVC.

Profile

 Aluminium cleanroom profile  from ITEM or Bosch

According to  customer requirements 

The protective enclosures can also be automatically controlled by us in temperature, relative humidity and pressure according to customer requirements.

Example of a protective enclosure for handling / robot area

Wall construction

Structure

single-shell wall structure

Skeleton construction as aluminum profile construction

Profile system 

without additional surface treatment / painting

The wall elements are closed up to approx. 10 cm above floor level.

gap of 10 cm between the wall and the floor

Surface elements mounted and sealed in the profile grooves.

Profile system

Aluminum, anodized

Profile dimension: 40 x 40 to 40 x 80 mm

Surface material

PVC sheets, white, thickness 4 mm: from 0.1 to 1.2 m from the top of the floor

Clear glass plastic panels, thickness 4 mm: from 1.2 m from the top of the floor

Wall openings

Openings as specified for:

Robot intervention in the mold area

Transportation belt

Ceiling construction

Structure

single-shell grid ceiling

Skeleton construction as aluminum profile construction

without additional surface treatment / painting

self-supporting construction

Surface elements mounted and sealed in the profile grooves

Profile

Aluminum, anodized

Profile dimension: 40 x 40 to 40 x 80 mm

Surface material

PVC sheets, white, thickness 4 mm

Ventilation / illumination

General

The room air supply is provided by a CAM clean room module,

setup of the clean room module CAM above the protective enclosure

(without cooling / humidification).

The illumination of the effective area is provided by lighting applications,

which are integrated in the clean room module.

Basic structure

Structure

Ionized air volume flow

Pre-filter, filter class: M5

High-performance HEPA filter, filter class: H 14

HEPA monitoring

Centrifugal fan with backward curved blades,

Fan monitoring

Control unit and cable remote control

as central control incl. switch module

bottom of page